2022-11-17 山特UPS-Ubuntu断电自动关机 - 来电自动开机

2022-11-17 山特UPS-Ubuntu断电自动关机 - 来电自动开机

1.安装 nut

apt-get install nut

2.使用lsusb查看是否接入ups

lsusb # 如果没有装一个 lsusb apt-get install lsusb

3.配置驱动

# 1.编辑ups配置文件 sudo vim /etc/nut/ups.conf,增加配置如下sudo vim /etc/nut/ups.confmaxretry = 3 [sanups] driver = usbhid-ups port = auto desc = "dev ups"

4.配置nut服务

# 1.新建ups用户sudo vim /etc/nut/upsd.users# 1.1 新增配置 [ups] password = 123456 upsmon master # 2.配置权限 chown root:nut /etc/nut/upsd.conf /etc/nut/upsd.users chmod0640 /etc/nut/upsd.conf /etc/nut/upsd.users # 3.修改模式为单机 sudo vim /etc/nut/nut.conf# 3.1 增加配置 MODE=standalone

5.启动服务

# 1.启动upsd服务 sudo /sbin/upsd # 2.查看启动服务信息 /bin/upsc sanups@localhost# ups.conf中的设备名 # 3.查看电量 /bin/upsc sanups@127.0.0.1 battery.charge

6.设置自动关机

# 当电量剩余20%时, nut服务会ups发送LOWBATT时通知机器关机 # 1. 配置upsmon sudo vim /etc/nut/upsmon.conf # 2.配置权限sudo chown root:nut /etc/nut/upsmon.conf sudo chmod0640 /etc/nut/upsmon.conf # 3.启动upsmon sudo /sbin/upsmon

7.配置高级电源策略-自定义事件(upssched)

# 自定义触发事件, 断电时自动关机 # 1. 配置运行upssched程序 sudo vim /etc/nut/upsmon.conf # 1.1 新增配置 # 触发条件,三个动作: 记录日志+通知用户事件+执行notifycmd NOTIFYCMD /sbin/upssched NOTIFYFLAG ONBATT SYSLOG+WALL+EXEC # 2.配置upsschedsudo vim /etc/nut/upssched.conf# 2.1 新增配置CMDSCRIPT /usr/local/bin/upssched PIPEFN /usr/local/bin/nut/upssched/upssched.pipe LOCKFN /usr/local/bin/nut/upssched/upssched.lock AT ONBATT * START-TIMER power-off300 # 300秒后自动关机 AT ONLINE * CANCEL-TIMER power-off AT ONLINE * EXECUTE power-on

8.配置事件触发脚本

# 1.配置触发脚本 sudo vim /usr/local/bin/upssched # 1.1 新增脚本 #!/bin/bash case $1in power-off) /sbin/upsmon -c fsd ;; *) logger -t upssched "Unrecognized command: $1" ;; esac # 1.2 邮件发送停电通知 (mail发邮件要记得装mail包哦!!!) # 1.2.1/sbin/upsmon -c fsd执行立刻关机操作 (FSD = "Forced Shutdown") #!/bin/bash case $1in power-off) echo "The UPS has been on battery for 300 seconds and foreman is about to shut down." \ | mail -s "NUT Master is about to shut down" lin@mail.com /sbin/upsmon -c fsd ;; power-on) echo "The UPS is online now and the server has started." \ | mail -s "NUT Master has started" lin@mail.com ;; *)logger -t upssched"Unrecognized command: $1" ;; esac

9.来电自动开机(以Dell服务器为例)

# 1.在开机过程中按键盘"F12",进入选择“BIOS SETUP”; # 2.选择“Power Management”; # 3.选择“AC Recovery”,点选“Power On”,点击“Apply”; # 4.勾选“Save as Custom User Setting”,点击OK; # 5.点击“EXit”退出即可; # 6.配置完成, 重新上电自动重启;

9.断电测试

# 重启一下 sudo /sbin/upsmon -s reload # 1. 断开UPS电源 # 2. 查看状态 sudo systemctl status nut-client # 3.查看控制台是否弹出通知 # 4.插上UPS电源 # 5.查看控制台是否弹出电源恢复通知 # 6.断电来电测试